Radon Testing and Mitigation in Iowa Schools

Iowa Code 280.32 requires schools to test for radon by 2027 and mitigate over 4.0 pCi/L. Testing protocols, scheduling, mitigation and reporting.

Updated 5 min read By the Radon Systems of Iowa team

Empty ground-floor classroom after hours with a radon monitor on a counter

School radon testing in Iowa is no longer a voluntary best practice. Iowa Code Section 280.32 requires every public school district to test its buildings, publish the results by 2027, and mitigate any building above 4.0 pCi/L. Licensed childcare centers have their own requirement to test within their first year of operation. For facilities directors and administrators, the questions are practical: what gets tested, when, how to fix high rooms in a large building, and how to report it without alarming parents.

Why Schools Are a Different Job

A school is not a big house. It has:

  • Large slabs often divided by grade beams and footings into separate sections.
  • Commercial air handlers that change building pressure by the hour.
  • Hundreds of occupants on the ground floor during the day and almost none at night.

A single test in one classroom says nothing about the room at the other end of the building. And in a county like Polk, which is EPA Radon Zone 1 with indoor averages reported around 7.3 to 9.2 pCi/L, districts should expect some rooms to test high.

The Testing Protocol

School and large-building testing follows the ANSI/AARST protocol for multifamily and large buildings. The core ideas:

Room coverage

Room typeUsually tested?
Ground-floor classroomsYes
Offices and nurse’s room on ground contactYes
Library, cafeteria, gym on ground contactYes, often with multiple devices
Rooms over crawlspaces or utility tunnelsYes
Upper-floor classroomsSometimes a sample, per protocol
Closets, restrooms, hallwaysUsually not

HVAC running normally

Testing must happen with the HVAC operating as it does when students are present. An empty building on a weekend setback gives misleading numbers. The heating season is the most informative time to test because it reflects the highest likely concentrations.

Quality control

Duplicates and field blanks confirm the devices are reading correctly, and results are reported room by room. A high initial short-term result is typically confirmed before major mitigation spending.

Scheduling Around Occupancy

Placement and pickup have to fit around:

  • Custodial shifts and building access.
  • Class periods, testing days and evening events.
  • HVAC programming, so the test reflects occupied conditions.
  • Secure device placement, out of reach and clearly labeled.

Continuous radon monitors are useful here because they flag a moved or disturbed device through motion and environmental data.

Fixing High Rooms in a Large Building

School mechanical room with HVAC units and a radon fan on a pipe

Multi-point sub-slab systems

Schools usually need several suction points spread across the slab, tied to one or more commercial-grade fans. Where grade beams split the slab, each section typically needs its own suction point, with balancing so the vacuum is even across zones. New school buildings should also incorporate radon-resistant new construction features from the start.

HVAC adjustments

In some newer buildings, adjusting ventilation to keep ground-floor rooms slightly pressurized helps. It works best paired with sub-slab suction rather than alone, since constant outdoor air intake drives up energy costs.

Sealing

Expansion joints, utility penetrations and tunnel connections are sealed with commercial-grade sealants so the system holds suction. Affected rooms are retested once the system is running.

Reporting to Boards and Parents

Facilities director presenting radon results to a school board

Because results are public, the report has to be clear. A useful package includes:

  • A room-by-room results table.
  • A color-coded building map.
  • A plain-language summary of what the numbers mean.
  • A mitigation plan and timeline for any rooms at or above 4.0 pCi/L.

High rooms are common in Central Iowa buildings and fixable with standard methods. Framing it that way keeps the conversation calm.

For administrators

Confirm the current statutory deadline and retest interval with the state before you build your schedule. The goal is testing and documentation that meet the official protocol and hold up to public review.

A Planning Sequence for Districts

  1. Gather floor plans, room-use lists and HVAC schedules.
  2. Prioritize the oldest buildings with the most ground-contact rooms.
  3. Test during a normal, occupied heating-season week.
  4. Review results and plan mitigation for any room at or above 4.0.
  5. Retest after mitigation and set a recurring schedule.

Local Support

Radon Systems of Iowa is Iowa HHS-credentialed for measurement and mitigation and NRPP certified. From our base in Altoona, we support the Southeast Polk Community School District area, nearby districts and licensed childcare centers with testing, multi-point mitigation and board-ready reporting. Send your building list and floor plans through our school radon services page for a project estimate, and we will help your Altoona-area buildings meet the 2027 requirement.

Quick Answers

Frequently Asked Questions

What does Iowa law require schools to do about radon?

Iowa Code Section 280.32 requires public school districts to test for radon and publish the results by 2027, and to mitigate buildings with levels over 4.0 pCi/L. Districts should confirm current deadlines and retest intervals with the state, since rules can be updated.

Which rooms in a school get tested?

Frequently occupied rooms in contact with the ground, or over crawlspaces or utility tunnels, are the priority: classrooms, offices, the nurse's room, libraries, gyms and cafeterias. Large rooms often get more than one device. Closets, restrooms and hallways usually do not.

Do licensed childcare centers have radon requirements too?

Yes. Licensed childcare centers in Iowa are required to test for radon within their first year of operation. The same protocol principles apply: frequently occupied ground-contact rooms, normal HVAC operation and credentialed testing.